Compact carbon monoxide detector and sensor in duct design with analogue outputs, relay alarms, and Modbus RTU support. More information
Out of stock - can be requested
| IP Rating | IP 65 |
| Measurement range | 0-300 ppm, 0-1000 ppm |
| Output signal | ModBus RTU RS485, 4-20 mA, 0...10 V |
| Power Supply | 24 VDC, 24 VAC |
| Type of gas | CO-Carbon Monoxide |
| Weight | 0.44 kg |
Technical sheet download
Download PDFData sheet - ENG download
Download PDFUser manual - ENG download
Download PDFThe Evikon E2608-CO-24-DM carbon monoxide detector is designed for monitoring CO concentration in industrial and commercial applications, particularly in underground garages, boiler rooms, or technical rooms. It uses an electrochemical sensor with high durability and fast response.
The device offers two analogue outputs, Modbus RTU digital communication, and two relay outputs for direct control of ventilation or signalling. The DM mounting version allows for easy installation directly into ductwork.
| Power Supply | 12...36 VDC / 24 VAC (version) |
| Detected Gas | Carbon Monoxide (CO) |
| Measurement Range | 0...300 ppm / 0...1000 ppm |
| Outputs | 2× 4-20 mA / 0-10 V, RS485 Modbus RTU |
| Relay Outputs | 2× SPST, max. 5 A |
| Protection | IP65 |
| Operating Temperature | –20...+50 °C |
| Dimensions | 87 × 82 × 55 mm |
| Certification | CE, EN 60079-29-1/2/3 |