Ultrasonic heat meter SHARKY 774 compact DN20, qp 2.5 m³/h, with wireless wM-Bus interface (868 MHz, OMS). For billing heat measurement in apartment buildings and district heating substations. MID class 2 approved. More information
Do týdne
| Connection size | DN 20 |
| Connection Type | External thread |
| Flow | 2.5 m3/h |
| M-BUS communication | wM-Bus |
| Medium | Water |
| Medium Temperature | 15...90°C |
| Pressure | PN 16 |
| Type of Meter | Ultrasonic |
| Weight | 1.25 kg |
SHARKY 774 compact is a compact ultrasonic heat meter from the German manufacturer Diehl Metering. It is designed for billing measurement of thermal energy consumption in both heating and cooling systems. This version has a nominal flow rate qp of 2.5 m³/h, nominal diameter DN20 (G1B), and a wireless wM-Bus (Wireless M-Bus) communication interface for radio data readout without the need to run bus cables.
The meter is intended for billing heat measurement in apartment buildings, flat interface units, heating circuits with heat pumps, and cooling systems. Thanks to its height of just 58 mm above the pipe axis, it also fits into compact interface units and narrow installation shafts where a mechanical meter may not have sufficient space.
Wireless wM-Bus communication makes retrofitting in existing apartment buildings much easier, where it is not practical to install bus cabling to every meter afterwards. The qp 2.5 m³/h version is the most powerful in the SHARKY 774 compact threaded range – it is suitable for flats with higher heat loss, shared domestic hot water heating circuits, smaller commercial premises, or locations where the design flow rate is close to the 1.5 m³/h limit and you want some reserve without the risk of overloading the meter.

Measurement principle
No wear, low pressure loss
1:100
qp/qi dynamic range
Service life
For wM-Bus operation, 2× AA batteries
11
years in standard mode
Resistance
MID electromagnetic immunity
E2 + M2
immunity class

The meter evaluates flow using the ultrasonic signal transit time method. There are no moving parts inside the pipe, which eliminates mechanical wear and allows the meter to maintain its accuracy throughout its service life. The low starting flow rate (4 l/h for qp 2.5 m³/h) ensures that the meter also captures small off-peak consumptions.
Ultrasonic measurement is insensitive to suspended particles in the heating water, which means the device performs well even in systems where mechanical meters tend to become clogged.
The meter is equipped with a wireless wM-Bus (Wireless M-Bus) interface in accordance with the Open Metering Standard (OMS), generation 3 profile A or generation 4 profile B. It transmits in the licence-free 868 MHz band, and communication is one-way – the meter sends a radio telegram with current values at regular intervals, which is received by an M-Bus receiver, concentrator, or mobile device.
Two readout modes are available. Standard mode (walk-by) sends data every 64 s and a synchronisation telegram every 900 s – it is suitable for walk-by readout by a technician using a handheld receiver. Rapid mode (drive-by) sends every 14 s and is intended for readout from a passing vehicle. The data telegram contains energy, power, volume, flow rate, temperatures, and historical data. A ZVEI optical interface is also available for local service readout.
Technical parameters:
An ultrasonic meter has no moving parts, so it does not suffer mechanical wear in operation and maintains its accuracy throughout its service life. It achieves lower pressure loss, has a wider dynamic range (qp/qi up to 1:100), and can detect very low flow rates from 4 l/h. At the same time, it is insensitive to dirt and suspended particles in the heating water, to which mechanical meters are prone.
The qp 2.5 m³/h version is sized for higher flow rates – typically for flats with higher heat loss, shared domestic hot water heating circuits, smaller commercial premises, or locations where the design flow rate exceeds 1 m³/h. The maximum flow rate qs is 5 m³/h. The qp 1.5 m³/h version (DN15 or DN20) is suitable for standard apartment circuits, while the qp 0.6 m³/h version is intended for flats with low heat loss and passive buildings. If the meter is undersized, it operates close to its overload limit and its service life is reduced; if oversized, it may lack resolution in the lower part of the flow curve.
wM-Bus (Wireless M-Bus) is the wireless version of the M-Bus standard for remote meter reading. The meter transmits a radio telegram at regular intervals, which is received by an M-Bus receiver, concentrator, or mobile device (notebook, tablet with reading application). Communication takes place in the licence-free 868 MHz band according to the Open Metering Standard (OMS) and is one-way – the meter only transmits, it does not receive. The main advantage over wired M-Bus is that you do not need to run bus cable to each meter, which is particularly suitable in existing apartment buildings.
Standard mode (walk-by) sends data every 64 seconds and is optimised for walk-by readout by a technician with a handheld receiver, who only needs to pass by the flat door or shaft. In this mode, the battery lasts up to 11 years. Rapid mode (drive-by) sends data every 14 seconds and is intended for readout from a passing vehicle, where the time available to capture the telegram is shorter. The higher transmission frequency reduces battery life to approximately 7 years. The mode is set during commissioning according to the planned readout method.
The meter can be installed in any position – horizontally, vertically on a riser or downpipe, and even inverted above the pipe axis. This orientation independence is due to the ultrasonic measuring principle, which does not require straight inlet and outlet lengths to the same extent as mechanical water meters.
For the wM-Bus version, the battery lasts up to 11 years in standard mode (walk-by, 64 s interval) and up to 7 years in rapid mode (drive-by, 14 s interval) under standard operating conditions. Higher ambient temperatures reduce battery life, which is why operation below 35 °C is recommended. The battery cannot be replaced by the user during operation; replacement is carried out by the manufacturer's service laboratory.
Yes. SHARKY 774 compact is approved in accordance with the MID directive (DE-13-MI004-PTB008) in accuracy class 2 and for cooling in accordance with PTB K7.2. It therefore meets the requirements for a legally controlled meter used for billing of heat and cooling. The meter belongs to environmental class E2 (electromagnetic immunity) and M2 (mechanical immunity), making it less susceptible to interference from PWM circulation pumps and similar sources.