Compact vortex flow sensor Huba Control type 210 for liquids with DN8, without moving parts, offering high accuracy and minimal pressure loss. More information
Out of stock - can be requested
| Bore size | DN 8 |
| Flow | 0.133 ... 2.210 m/s |
| Measurement range | 0.9 ... 15 l/min |
| Output | 0-10 V |
| Temperature | -40 ... 125 °C |
| Weight | 0.05 kg |
Manual download
Download PDFProspectus download
Download PDFCatalog sheet EN download
Download PDFThe Huba Control type 210 flow sensor in DN8 design is intended for reliable measurement of liquid media flow in heating and cooling circuits, water distribution systems, and other applications. It uses the vortex principle with a piezoelectric sensor, so it contains no moving parts – making it resistant to impurities in the medium and requiring very low maintenance. The sensor's design ensures minimal pressure loss and stable measurement even across a wide temperature range. The measuring element is not in direct contact with the medium, which contributes to long service life and excellent chemical resistance. The design is also suitable for drinking water according to relevant approvals.
| Nominal Diameter | DN 8 |
| Flow Measurement Range | 0.9–15 l/min |
| Measurement Principle | vortex, piezoelectric sensor |
| Accuracy (water) | < 1% FS up to 50% range, 2% of measured value above 50% |
| Output Signal | frequency / 0...10 V / 4...20 mA (depending on design) |
| Power Supply | 4.75...33 VDC (frequency), 11.5...33 VDC (0...10 V), 8...33 VDC (4...20 mA) |
| Medium Temperature | -40...+125 °C |
| Max. Operating Pressure | 12 bar at +40 °C (long-term) |
| Electrical Connection / Protection | M12x1 connector, IP65 |
| Seal Material | EPDM |
We respond to your product queries as quickly as possible, usually within 24 hours.