Vortex flow sensor Huba Control type 210 for DN20 without moving parts, with high accuracy and minimal pressure loss. More information
Out of stock - can be requested
| Bore size | DN 20 |
| Flow | 0.265 ... 4.509 m/s |
| Measurement range | 5.0 ... 85 l/min |
| Output | 0-10 V |
| Temperature | -40 ... 125 °C |
| Weight | 0.30 kg |
Manual download
Download PDFProspectus download
Download PDFCatalog sheet EN download
Download PDFThe Huba Control flow sensor type 210 in size DN20 is designed for precise measurement of liquid flow in heating and water circuits. It utilizes a vortex measuring principle with piezoelectric sensing, which is not dependent on the medium's temperature and ensures stable results even during long-term operation. The construction without moving parts means high resistance to impurities in the medium and simultaneously very low pressure loss. The liquid flowing through the medium is not in contact with the sensing element, which supports a long lifespan. The sensor is available with frequency or analog output and is also suitable for applications requiring approval for drinking water.
| Nominal Diameter | DN 20 |
| Flow Measurement Range (DN20) | 5.0–85 l/min |
| Measuring Principle | Vortex, piezoelectric sensor |
| Accuracy (water) | < 1% FS up to 50% range, < 2% of measured value above 50% FS |
| Medium Temperature | -40...125 °C |
| Ambient Temperature | -15...85 °C |
| Max. Medium Pressure | 12 bar at +40 °C (long-term) |
| Power Supply / Output | Depending on version: frequency / 0–10 V / 4–20 mA |
| Electrical Connection / Protection | M12x1, IP65 |
| Materials in Contact with Medium | ETFE (paddle), PA6T/6I (body), EPDM/FPM (seals depending on version) |
| Certification | CE, drinking water approval KTW/W270/WRAS/ACS (depending on version) |
We respond to your product queries as quickly as possible, usually within 24 hours.