Honeywell V5832 Two-Way Control Valve DN40 (V5832B2117)

Honeywell V5832 Two-Way Control Valve DN40 (V5832B2117)

HONEYWELL
  • Product code: V5832B2117
  • EAN : 4019837046514
  • Manufacturer code: V5832B2117
  • Warranty: 2 years

Honeywell V5832B DN40 control valve (kVs 25) for controlling hot and chilled water in fan coil units and heaters. Pressure-balanced plug, PN16, temperature range 2–130 °C. More information

  • Availability

    Out of stock - can be requested

  • Out of stock  
List price € 430,14
Price excluding VAT € 284,39
Price with VAT 21 % € 344,11
+

Parameters and catalogs

Flow 25 m3/h
Medium Temperature 2...130 °C
Nominal diameter DN 40
Pressure PN 16
Weight 0.67 kg

Honeywell V5832B DN40 (V5832B2117) is a two-way linear control valve with a pressure-balanced plug, designed for precise control of hot or chilled water flow. The valve operates at a nominal pressure of PN16 with a kVs flow coefficient of 25 and a temperature range of 2–130 °C. It is installed in combination with small Honeywell electric linear actuators.

Typical applications

The V5832B valve is primarily intended for heating and cooling control in systems with fan coil units, small heaters (reheaters) and heat recovery units in commercial buildings. Thanks to its compact dimensions and DN40 size with kVs 25, it can also meet more demanding flow requirements in smaller air-conditioning circuits. The valve is installed in the return line, with water always flowing from port A to port B.

Honeywell V5832B DN40 control valve – left-hand view
Diagram of the pressure-balanced plug of the V5832B valve

Pressure-balanced plug

Thanks to the pressure-balanced plug, the close-off pressure is equal to the system pressure – specifically up to 1,000 kPa with actuators rated at 300 N or 400 N. This ensures reliable shut-off even at high differential pressure without the need for an oversized actuator. The valve handles flow control over a 50:1 range, with a linear flow characteristic.

Manual setting without actuator

The valve is supplied with an adjusting cap that allows manual operation of the stem without an actuator connected. This function is practical during filling or initial heating/cooling of the system during the construction phase, when the control system is not yet in operation. The cap is removed only when the actuator is installed.

Technical parameters (V5832B2117):

  • Nominal diameter: DN40 (1½")
  • kVs flow coefficient: 25
  • Nominal pressure: PN16
  • Max. close-off pressure: 1,000 kPa (with both 300 N and 400 N actuators)
  • Stem travel: 6.5 mm
  • Flow characteristic: linear
  • Rangeability: 50:1
  • Medium temperature range: 2–130 °C
  • Medium: water, max. 50% glycol
  • Valve body: dezincification-resistant brass
  • Stem: stainless steel
  • Plug: brass
  • Leakage: 0.05% of kVs
  • Connection: G2¼" male thread (with AC-40T or AC-40TF installation set)

Frequently asked questions

The V5832B2117 valve is compatible with small Honeywell electric linear actuators rated at 300 N (e.g. M7410C1015, M7410E1028) or 400 N (e.g. ML6435B, ML7430E, ML7435E). When using either a 300 N or 400 N actuator, the max. close-off pressure is 1,000 kPa.

The V5832B two-way valve requires two installation sets – one for each port (inlet A and outlet B). For DN40, these are the AC-40T sets (R1½" male thread) or AC-40TF (Rp1½" female thread). The sets are not included with the valve and must be ordered separately.

The valve is installed in the return line, with the medium always flowing from port A (inlet) to port B (outlet). The stem must not point downwards. The recommended tightening torque for the connections is 25–30 Nm. Water quality must comply with the requirements of VDI 2035.

Yes. The V5832B valve is designed for water with a maximum glycol content of 50%, making it suitable for cooling circuits with antifreeze mixture as well. The medium temperature range is 2–130 °C.

We respond to your product queries as quickly as possible, usually within 24 hours.