Gas detector for refrigerants EVIKON E2610-HFC, alarm signalling: LED light + audible, measuring range: 0...500 ppm R32. More information
Delivery to Belgium (days are avarages)
DHL Express: 1.2 workdays, € 16,94
| Detector type | Stationary |
| Output signal | Switching relay |
| Power Supply | 230 VAC |
| Type of gas | HFC Refrigerants - R32 |
| Weight | 0.17 kg |
Catalog sheet eng download
Download PDF
The gas concentration sensor (gas detector) is designed to detect and provide early warning of a hazardous (explosive) concentration of the monitored refrigerant. The sensor is suitable for detecting refrigerant leaks from refrigeration equipment, air conditioning systems and heat pumps.
The sensor is equipped with two-stage signalling – visual (LED) and audible (85 dB). Two output relays with changeover contacts can be used for remote signalling or ventilation control. The set switching points are: Relay 1 = 200 ppm, Relay 2 = 500 ppm.
A temperature-compensated, durable semiconductor sensor is used for detection. The sensor service life is more than 5 years. The sensor is non-selective = calibrated to R32 -> it also responds to other refrigerants (R-12, R-123, R-125, R-134a, R-143, R-22, R-404a, R-407c, R-410a, R1234yf and others), flammable gases, solvent vapours and cleaning agents. The recommended coverage area for one sensor is 80-120 m2, 5-6 m radius.
Each sensor is factory-calibrated and an English calibration certificate is included in the package.
The detector is equipped with a test button that initiates the sensor self-diagnostics. The diagnostics check the electrical response of the sensor and after 64 seconds the device returns to stable measurement. The diagnostics do not activate the relays.
Tip: Get automatic reminders of the statutory calibration date via the service www.kalibrovat.cz
We respond to your product queries as quickly as possible, usually within 24 hours.
Nenašli jste to, co jste chtěli vědět?