Flood Sensor Regmet DZ1. Designed for signalling fault conditions. Transistor outputs OUT C, OUT E. More information
Delivery to Belgium (days are avarages)
DHL Express: 1.2 workdays, € 16,94
| Design | On DIN rail |
| IP Rating | IP 65 |
| Number of levels | 1 |
| Power Supply | 24 VDC, 12 VDC |
| Weight | 0.13 kg |
Datasheet download
Download PDFFlood Sensor Regmet DZ1 is designed for signalling fault conditions (e.g., water leakage) in heat exchange stations, boiler rooms, and similar facilities. The flood sensor is powered by a direct current voltage of 12-30VDC and includes open emitter type output terminals. Therefore, the signalling can be switched to the positive or negative pole of the power supply voltage. The flood sensor is intended for mounting on a DIN rail. Suitable sensing probes are DS PROBES.
Upon connecting the probe to the sensor input and joining the probe electrodes, the red LED on the front of the sensor lights up, and the outputs are activated or deactivated. The state of the outputs (activation/deactivation) is determined by switching the jumper to position A or B. The setting jumpers are accessible after removing the right side cover.