Questions? +32 460 226 991 (English). EU-wide delivery!

Siemens QAD 2012 Surface-Mounted Temperature Sensor (QAD2012)

Extended warranty 5 years

Siemens QAD 2012 Surface-Mounted Temperature Sensor (QAD2012)

SIEMENS
  • Product code: QAD2012
  • EAN : 7612914048684
  • Manufacturer code: QAD2012
  • Warranty: 5 years

The QAD2012 strap-on temperature sensor is designed for measuring pipe temperatures. This sensor uses a Pt 1000 sensor with a temperature range from -30 to +130 °C. More information

  • Delivery

    Delivery to Belgium (days are avarages)

    FedEx:
    2.7 workdays € 7,02
    Bpost HD (Home Delivery):
    4.4 workdays € 10,64
    BPost - PP (Pick-up Point):
    3.9 workdays € 9,91
    FedEx Priority:
    1.7 workdays € 12,71
    DHL Express:
    1.2 workdays € 16,94

    DHL Express: 1.2 workdays, € 16,94

  • More than 5 pcs in stock  
     
List price € 32,22
Price excluding VAT € 19,97
Price with VAT 21 % € 24,16
+

Parameters and catalogs

Measurement range -30...130 °C
Sensor type Pt 1000/3850
Weight 0.09 kg

Technical sheet en download

Download PDF

The QAD2012 strap-on temperature sensor is designed for measuring pipe temperatures. This sensor uses a Pt 1000 sensor with a temperature range from -30 to +130 °C and a time constant of 3 seconds. The sensor is suitable for applications involving the control or limitation of the medium's temperature in pipes.

Main Functions

  • Pipe temperature measurement
  • Flow temperature control and limitation
  • Return temperature limitation
  • Hot water temperature control

Technical Specifications

  • Temperature range: -30...+130 °C
  • Time constant: 3 seconds
  • Accuracy: according to Pt 1000 characteristics
  • Protective cover: IP42 according to IEC 60529
  • Measurement type: passive

Mechanical Design

  • Two-piece plastic housing with removable cover
  • Flexible connecting plate for adapting to the pipe surface
  • Mounting strap for pipe diameters from 15 to 140 mm
  • Terminal block for max. 1x 2.5 mm2

Installation Instructions

  • Placement according to application: in the heating system directly behind the pump or after the mixing valve
  • Proper fastening using the adjustable strap
  • Water must be well mixed at the temperature measurement point

We respond to your product queries as quickly as possible, usually within 24 hours.

Nenašli jste to, co jste chtěli vědět?