Temperature Sensor Johnson Controls TE-6311P (TE-6311P-1)

Temperature Sensor Johnson Controls TE-6311P (TE-6311P-1)

JOHNSON CONTROLS
  • Product code: TE-6311P-1
  • Manufacturer code: TE-6311P-1
  • Warranty: 2 years

Johnson Controls TE-6311P-1 – duct-mounted resistance temperature sensor for HVAC systems. Type 1k ohm nickel, accuracy ±0.19 °C, 203 mm probe, plastic enclosure with NPT thread. More information

  • Delivery

    Delivery to Belgium (days are avarages)

    FedEx:
    2.7 workdays € 7,02
    Bpost HD (Home Delivery):
    4.4 workdays € 10,64
    BPost - PP (Pick-up Point):
    3.9 workdays € 9,91
    FedEx Priority:
    1.7 workdays € 12,71
    DHL Express:
    1.2 workdays € 16,94

    DHL Express: 1.2 workdays, € 16,94

  • In stock 3 pcs  
     
List price € 155,92
Price excluding VAT € 96,64
Price with VAT 21 % € 116,93
+

Parameters and catalogs

Design plastic/metal box
Operating temperature -50...220
Stem length 203 mm
Weight 1.00 kg

Johnson Controls TE-6311P-1 is a passive resistive duct temperature sensor designed for use in HVAC systems. The sensor operates on the resistance measurement principle – 1k ohm thin-film nickel type – and, as a two-wire device, transmits the signal directly to a controller or DDC system. It is supplied with a plastic enclosure (TE-63xxP) and an 8 in. (203 mm) probe.

Typical applications

The TE-6311P-1 sensor is designed for measuring air temperature inside ventilation ducts in buildings such as offices, schools, hospitals, industrial facilities, and shopping centres. It serves as an input signal for temperature controllers, fan coil units, VAV systems, or central BMS. The 203 mm probe covers standard duct cross-sections; for larger cross-sections or environments with temperature stratification, it is advisable to combine multiple sensors in a series-parallel configuration. The plastic enclosure with 1/2–14 NPT internal thread allows connection to electrical conduit.

Johnson Controls TE-6311P-1 – duct temperature sensor with plastic enclosure

Sensor technical parameters:

  • Sensor type: 1k ohm thin-film nickel
  • Reference resistance: 1,000 Ω at 70 °F (21 °C)
  • Accuracy: ±0.34 °F (±0.19 °C) at 70 °F (21 °C)
  • Temperature coefficient: approximately 3 Ω/°F (5.4 Ω/°C)
  • Probe length: 8 in. (203 mm), diameter 0.25 in. (6.35 mm), stainless steel
  • Enclosure operating temperature: −50 to +122 °F (−46 to +50 °C)
  • Probe operating temperature: −50 to +220 °F (−46 to +104 °C)
  • Electrical connection: 22 AWG (∅ 0.6 mm), lead length 6 in. (152 mm)
  • Enclosure: rigid thermoplastic with 1/2–14 NPT internal thread; aluminium mounting plate
  • Enclosure dimensions: 152 × 35 × 70 mm (H × W × D)
  • Weight: 0.4 lb (0.18 kg)

Frequently asked questions

The TE-6311P-1 is a passive two-wire device with a resistive output – it does not require a power supply. You simply connect the two wires directly to the resistive input of the controller or DDC module. The controller itself measures the probe resistance and converts it into temperature according to the 1k ohm nickel characteristic.

The TE-6311P-1 model with plastic cover does not in itself meet plenum rating requirements. To comply with UL 1995, the plastic cover must be replaced with the TE-6001-13 kit (metal cover with gasket). TE-63xxM or TE-63xxE models meet plenum requirements without modification.

Yes, the TE-6311P-1 model (203 mm probe) can be fitted into a thermowell. The appropriate probe holder must be ordered separately: for the TE-6300W-110 thermowell (stainless steel, immersion depth 114 mm, 1/2–14 NPT thread), use the TE-6300-605 adaptor, which is included in the accessories for P-models.

The plastic enclosure (TE-63xxP) has a thermoplastic conduit box with a 1/2–14 NPT thread and an aluminium mounting plate – suitable for standard installations without a plenum requirement. The metal enclosure (TE-63xxM) is made of corrosion-resistant steel, complies with UL 1995 plenum requirements without modification, and also offers direct mounting into a 1/2–14 NPT thermowell without an adaptor. For applications requiring compliance with the IMC code, the TE-6300-613 kit is additionally required for the M-model.

We respond to your product queries as quickly as possible, usually within 24 hours.

Nenašli jste to, co jste chtěli vědět?