Questions? +32 460 226 991 (English). EU-wide delivery!

VOC Sensor EVIKON E2618-VOC-DM (E2618-VOC-DM)

VOC Sensor EVIKON E2618-VOC-DM (E2618-VOC-DM)

EVIKON
  • Product code: E2618-VOC-DM
  • Manufacturer code: E2618-VOC-DM
  • Warranty: 2 years

EVIKON E2618-VOC-DM VOC sensor for reliable monitoring of solvent vapours in production facilities, warehouses and paint shops. Suitable for personal protection and for preventing explosive atmospheres. More information

  • Availability

    Out of stock - can be requested

  • Out of stock  
Price excluding VAT € 304,00
Price with VAT 21 % € 367,84
+

Parameters and catalogs

Detector type For HVAC duct
Measurement range 0...100% LEL
Output signal ModBus RS485, 2x Analog Output 4-20mA/0-10V
Power Supply 12...36 VDC
Type of gas VOC-Volatile Organic Compounds
Weight 0.26 kg

The E2618-VOC volatile organic compounds sensor is part of the PluraSens® product range, which includes multi-purpose instruments for gas detection in building and industrial environments. The device is designed to monitor the concentration of volatile organic compounds (VOCs) in air where they may accumulate as a result of technological processes, the use of solvents, or insufficient ventilation. Typical applications include chemical stores, paint shops, spray booths, production facilities, and other technical areas where continuous VOC level monitoring is required for both personal health protection and operational safety. The unit is equipped with both an analogue output (optionally 4–20 mA or 0–10 V) and an RS-485 digital interface using the standard Modbus RTU communication protocol. These outputs enable straightforward integration into measurement and control systems, building management systems (BMS), or safety systems. The instrument is intended for fixed installation and is designed to meet the requirements of technical and industrial premises in terms of ingress protection, reliability, and ease of maintenance.

The device is housed in a wall-mounted enclosure with IP65 protection, ensuring resistance to dust and water. The sensor has no visual or audible alarm and is intended for sensing and transmitting measured data to a control panel or higher-level system.

Typical applications:

The E2618-VOC sensor is intended for monitoring volatile organic compounds in environments such as paint shops, solvent stores, production halls, chemical plants, and other enclosed areas where organic vapours may accumulate. The instrument helps prevent health risks associated with VOC exposure and also contributes to early detection of potentially hazardous concentrations from a fire safety perspective.

Volatile organic compounds (VOCs):

Volatile organic compounds (VOCs) are organic compounds that readily evaporate at normal operating temperatures. They include, for example, acetone, ethanol, toluene, or xylene. These substances are commonly found in industrial processes, coatings, cleaning agents, or solvents. At higher concentrations they may be harmful to health, and some can form explosive mixtures with air. For this reason, monitoring is particularly important in enclosed or poorly ventilated areas.


Calibration certificate

Each Evikon gas detector package includes a factory calibration certificate. The calibration certificate is in English. Gas concentration measurement is affected by operating temperature and humidity. Therefore, calibration at the detector factory is carried out with enhanced safety in mind.


Key features:

  • Detected substances: VOC – volatile organic compounds, e.g. acetone, ethanol, toluene, xylene
  • Sensor type: metal-oxide semiconductor sensor with diffusion sampling
  • Measuring range: 0...100 % LEL
  • Resolution: 0.1 % LEL
  • 2x analogue output 4–20 mA / 0–10 V – user-selectable
  • Continuous measurement
  • Expected sensor lifetime: > 5 years
  • Suitable for monitoring both toxic and potentially explosive VOC concentrations

Factory settings:

  • Calibration gas: Toluene
  • Measuring range: 0...100 % LEL
  • Diffusion version
  • Modbus RTU Slave ID=1
  • Analogue output settings:
    • AO1 = 0...100 % LEL
    • AO2 = 0...100 % LEL

Specifications:

  • Power supply: 12...36 VDC
  • 2x analogue output 4–20 mA / 0–10 V – user-selectable
  • Digital interface: RS485, Modbus RTU
  • Operating conditions: -30...+70 °C, < 95 % RH
  • Enclosure dimensions: H82 × W80 × D55 mm
  • Protection class: IP65

This sensor is suitable for monitoring volatile organic compounds in a range of industrial and technical environments. It offers stable performance, long sensor lifetime, and easy integration into higher-level systems, making it a practical solution for long-term use across a wide spectrum of applications.

We respond to your product queries as quickly as possible, usually within 24 hours.

Nenašli jste to, co jste chtěli vědět?